What are the new Condensation Management requirements for Roofs?
Roofs are susceptible to condensation risks as water vapour is lighter than air and tends to rise. The NCC 2022 requires roofs to have an escape path for water vapour in the form a space or cavity. The roof space needs to be 20mm in height and located immediately above the primary insulation layer (insulation batts) OR immediately above sarking with a class 4 vapour permeance above the primary insulation layer OR immediately above the ceiling insulation.
Roof spaces also need to be ventilated through evenly distributed openings. The opening details depend upon the roof pitch and type roof shown in Table 10.8.3 which is in the Housing Provisions. An example of the location of such opening is in the eave.